468
Temperature Input Unit Functions
Section 11-5
Note
When setting the alarm value, allow for the decimal point position or the 1/100
Display Mode for each input. Always correct the alarm value after changing
the display mode or replacing the input with one that has a different decimal
point position.
Example: Alarm value setting for 250
°
R thermocouple (normal display) setting: 00250 decimal
T thermocouple (normal display) setting: 02500 decimal
Setting for any input with 1/100 display: 25000 decimal
5.
To set the hysteresis value, input the desired value in the
Hysteresis
Field.
Note
The hysteresis value set for the comparator function is also used by the top/
valley hold function.
6.
To set the OFF delay function, input the desired value in the
Comparator
Off Delay
Field.