310
Analog Output Slave Units
Section 6-5
6-5
Analog Output Slave Units
6-5-1
Two-point Analog Output Slave Unit
CRT1-DA02
General Specifications
Note
The specified accuracy does not apply below 0.2 mA when using the 0 to
20 mA range.
Component Names and Functions
Item
Specification
Voltage output
Current output
Model
CRT1-DA02
Output signal ranges
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
0 to 20 mA
4 to 20 mA
External output allowable load resistance
1 k
Ω
min.
600
Ω
max.
Resolution
1/6,000 (full scale)
Overall accuracy
25°C
±
0.4% FS
±
0.4% FS (See note.)
–10 to 55°C
±
0.8% FS
±
0.8% FS (See note.)
Conversion time
2 ms/ 2 points
DA conversion data
–10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
DA conversion range:
±
5% FS of the above data ranges.
Isolation method
Photocoupler isolation (between output and communications lines)
No isolation between output signal wires.
Mounting
DIN Track mounting
Power supply type
Multi-power supply
Communications power current consumption
125 mA max. for 24-VDC power supply
205 mA max. for 14-VDC power supply
Weight
155 g
Communications
connector
MS NS
WORD NODE ADR
X10
[0-63]
X1
ON
SW
A/D
1
2
3
4
5
6
7
8
INPUT
RANGE
CH0,1
INPUT
RANGE
CH2,3
RSV
LSET
1 2 3 4 5 6 7 8
012
3
45678
9
012
3
45678
9
ANALOG TERMINAL
CRT1
CRT1-
DA02
DA02
DIP switch for
setting the output
ranges
Removable terminal block
for analog I/O
Node address switches:
×
10 and
×
1 (from left)
Communications
indicators: MS and NS
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...