339
Temperature Input Units
Section 7-5
4.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
Temperature Ranges
by Input Type
The following tables show the temperature ranges for each input type.
CRT1-TS04T
CRT1-TS04P
Note
The temperature ranges listed above are the ranges in which the input accu-
racy is within the specified range.
Convertible
Temperature Ranges
The convertible data range depends on the selected input type, as shown in
the following tables.
CRT1-TS04T Data Ranges
Input type
Temperature range (°C)
Temperature range (°F)
R
0 to 1,700
0 to 3,000
S
0 to 1,700
0 to 3,000
K (
−
200 to 1300
°
C)
−
200 to 1,300
−
300 to 2,300
K (0.0 to 500.0
°
C)
0.0 to 500.0
0.0 to 900.0
J (
−
100 to 850
°
C)
−
100 to 850
−
100 to 1,500
J (0.0 to 400.0
°
C)
0.0 to 400.0
0.0 to 750.0
T
−
200.0 to 400.0
−
300.0 to 700.0
E
0 to 600
0 to 1,100
L (
−
100 to 850
°
C)
−
100 to 850
−
100 to 1,500
L (0.0 to 400
°
C)
0.0 to 400.0
0.0 to 750.0
U
−
200.0 to 400.0
−
300.0 to 700.0
N
−
200 to 1,300
−
300 to 2,300
W
0 to 2,300
0 to 4,100
B
100 to 1,800
300 to 3,200
PL2
0 to 1,300
0 to 2,300
Input type
Temperature range (°C)
Temperature range (°F)
PT100 (
−
200 to
850
°
C)
−
200.0 to 850.0
−
300.0 to 1,500.0
PT100 (
−
200 to
200
°
C)
−
200.0 to 200.0
−
300.0 to 380.0
Input type
°
C
Display
°
F
Display
R
−
20 to 1,720
FFEC to 06B8
−
20 o 3,020
FFEC to 0BCC
S
−
20 to 1,720
FFEC to 06B8
−
20 to 3,020
FFEC to 0BCC
K (
−
200 to
1,300
°
C)
−
220 to 1,320
FF24 to 0528
−
320 to 2,3200
FEC0 to 0910
K (0.0 to
500.0
°
C)
−
20.0 to 520.0
FF38 to 1450
−
20.0 to 920.0
FF38 to 23F0
J (
−
100 to
850
°
C)
−
120 to 870
FF88 to 0366
−
120 to 1,520
FF88 to 05F0
J (0.0 to
400.0
°
C)
−
20.0 to 420.0
FF38 to 1068
−
20.0 to 770.0
FF38 to 1E14
T
−
220.0 to 420.0
F768 to 1068
−
320.0 to 720.0
F380 to 1C20
E
−
20 to 620
FFEC to 026C
−
20 to 1,120
FFEC to 0460
L (
−
100 to
850
°
C)
−
120 to 870
FF88 to 0366
−
120 to 1,520
FF88 to 05F0
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...