431
Analog I/O Slave Unit Functions
Section 11-4
One-shot Time Setting
1,2,3...
1.
Input the desired value in the
SHOT Off Delay
Field of the
Top/Valley
Tab
under the
Function Choice
heading.
2.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button.
3.
Click the
OK
Button and exit the window.
Rate of Change
Calculation
The rate of change can be obtained for each sampling cycle set for the analog
input data. This function calculates the difference between each set sampling
cycle and value obtained in the previous cycle. The default setting for the
sampling cycle is 100 ms and the sampling cycle setting range is 10 to
65,530 ms (in units of 10 ms).
Note
If the sampling cycle is set to a small value, the rate of change will be sensitive
to small changes. If the analog data is subject to minute fluctuations, and the
sampling cycle is shorter than the cycle of fluctuation, the fluctuation will be
0
Analog input value
Analog data
Rate of change
Time
Differentiation data
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...