39
Communications Cable Wiring Examples
Section 2-4
2-4
Communications Cable Wiring Examples
The following wiring is required in a CompoNet Network.
• Two communications signal lines (communications data): BDH (communi-
cations data high) and BDL (communications data low)
• Two communications power supply lines (power for communications and
internal Slave Unit circuits): BS+ (communications power supply plus
side) and BS
−
(communications power supply minus side)
The wiring method depends on the type of cable that is used.
2-4-1
Round Cable I
• Connect the two communications signal lines in parallel between the Mas-
ter Unit or Repeater Unit and multiple Slave Units.
• Use Open Type Connectors (DCN4-TB4, for connecting Units) to connect
Communications Cables to Master Units, Repeater Units, and Slave
Units.
• To supply the communications power (24 VDC), connect the two commu-
nications power supply lines to each Slave Unit separately from the Com-
munications Cables.
• Power is not supplied to the Master Unit or Repeater Units.
• A Terminating Resistor (DRS1-T) must be connected at the end of the
network.
Slave Units can also be connected in parallel using multidrop connections.
BDL
BDH
BDL
BDH
BDL
BDH
BS
−
BS+
BS
−
BS+
BS
−
BS+
Terminating Resistor
(121
Ω
)
Two communications
signal lines
Communications
Communications
Slave Unit
Slave Unit
Slave Unit
24-VDC
communications
power supply
24-VDC
communications
power supply
24-VDC
communications
power supply
Master Unit or
Repeater Unit
Open Connector
Open Connector
Relay terminal block
Commu-
nications
BS+
BS
−
BDL
BDH
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...