508
CompoNet Explicit Messages
Appendix A
Setting and Monitoring the Outputs
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode
Read Reads the monitor mode
for maintenance infor-
mation of the output (No.
1 to 32) specified by the
Instance ID.
0E hex
09 hex
01 to 20
hex
65 hex
---
1 byte
00 hex: Total
ON time
mode
01 hex: Con-
tact opera-
tion counter
mode
Write Writes the monitor mode
for maintenance infor-
mation of the output (No.
1 to 32) specified by the
Instance ID.
10 hex
09 hex
01 to 20
hex
65 hex
1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
Set Value
for Output
Total ON
Time or
Contact
Operation
Counter
Read Reads the set value for
the total ON time (unit: s)
or number of contact
operations (unit: opera-
tion) for the output (No. 1
to 32) specified by the
Instance ID.
0E hex
09 hex
01 to 20
hex
68 hex
---
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
Write Writes the set value for
the total ON time (unit: s)
or number of contact
operations (unit: opera-
tion) for the output (No. 1
to 32) specified by the
Instance ID.
10 hex
09 hex
01 to 20
hex
68 hex
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
---
Output
Total ON
Time or
Contact
Operation
Counter
Read
Read Reads the total ON time
(unit: s) or number of
contact operations (unit:
operation) for the output
(No. 1 to 32) specified by
the Instance ID.
0E hex
09 hex
01 to 20
hex
66 hex
---
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
Reset for
Output
Total ON
Time or
Contact
Operation
Counter
Reset
Reset Resets the total ON time
(unit: s) or number of
contact operations (unit:
operation) for the output
(No. 1 to 32) specified by
the Instance ID to 0.
05 hex
09 hex
01 to 20
hex
66 hex
---
---
Monitor
Status for
Output
Total ON
Time or
Contact
Operation
Counter
Read
Read Reads the monitor sta-
tus for total ON time or
contact operation
counter for the output
(No. 1 to 32) specified by
the Instance ID.
0E hex
09 hex
01 to 20
hex
67 hex
---
1 byte
00 hex:
Within range
01 hex: Out
of range
(over the
monitor
value)
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...