157
Units with Screw Terminal Blocks
Section 5-3
Indicator Section
Communications
Indicators
Refer to
4-1-3 Communications Indicators
.
I/O Indicators
The meanings of the output indicators are given in the following table.
The detected status is also shown below for Slave Unit with detection func-
tions.
CRT1-OD08TAH(-1) Only
Setting the Node
Address
The node address is set as a decimal number with the 10s digit set on the left
rotary switch and the 1s digit set on the right rotary switch. (The maximum
node address is 63.)
The setting on the rotary switches is read when power is turned ON.
Internal Circuits
CRT1-OD08TA (NPN)
Name
LED status
I/O status
Meaning
0 to 7
Lit yellow.
Output ON
The output is ON.
Not lit.
Output OFF
The output is OFF.
Name
LED status
I/O status
Meaning
0 to 7
Lit red.
Short-circuit
detection
A load short-circuit
occurred.
Flashing
red.
Disconnection
detection
A line is not connected.
Not lit.
Normal status
The Unit is operating
normally.
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1s digit of node address
10s digit of node address
BS+
BDH
BDL
BS-
V 24 VDC
G
V
G
Output (0 to 7)
Photocoupler
Voltage
drop
Physical
layer
DC-DC
converter
(not isolated)
Internal circuits
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...