482
Temperature Input Unit Functions
Section 11-5
8.
Adjust the lower limit value. Input 0 mV from the reference voltage/current
generator (STV) to the Temperature Input Unit's input terminals. Wait at
least 1 minute for the input to stabilize.
9.
Click the
Fix lower adjusting Value
Button in the Adjustment Window to
write the adjustment value.
10. Adjust the upper limit value. Input the upper limit voltage from the reference
voltage/current generator to the input terminals of the input to be adjusted.
Refer to the following table for the appropriate voltage. Wait at least 1
minute for the input to stabilize.
11. Click the
Fix upper adjusting Value
Button and write the adjustment val-
ue.
Type
Input voltage
K (
−
200 to 1300
°
C)
50 mV
K (0.0 to 500.0
°
C)
20 mV
J (
−
100 to 850
°
C)
50 mV
J (0.0 to 400.0
°
C)
20 mV
T
20 mV
L (
−
100 to 850
°
C)
50 mV
L (0.0 to 400.0
°
C)
20 mV
U
20 mV
N
50 mV
PL2
50 mV
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...