337
Temperature Input Units
Section 7-5
Node Address
Settings
The node address of the Temperature Input Unit is set as a decimal value
using the left rotary switch for the ten's digit and the right rotary switch for the
one's digit. (Up to 63 nodes can be set.)
Note
The rotary switch settings are read when the power is turned ON.
Setting the Input Type
Setting with the DIP
Switch
The input type can be set using the DIP switch or the CX-Integrator.
Set each pin according to the following table.
CRT1-TS04T
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
Node address, x1
Node address, x10
Pin No.
Setting
Specifications
SW1
Sets the input type (input
range)
Refer to the following table.
Default setting: All pins OFF
SW2
SW3
SW4
SW5
Always OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
SW6
Selects °C or °F display.
OFF: °C conversion
ON: °F conversion
Default setting: OFF
SW7
Always OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
SW8
Selects the input type set-
ting method.
OFF: Set with CX-Integrator.
ON: Set with DIP switch.
Note
When the input type is set with the DIP
switch, all inputs are set to the same
input type.To set different input types,
use the CX-Integrator to make the set-
tings.
SW1
SW2
SW3
SW4
Input type
OFF
OFF
OFF
OFF
R
ON
OFF
OFF
OFF
S
OFF
ON
OFF
OFF
K (
−
200 to 1300
°
C)
ON
ON
OFF
OFF
K (0.0 to 500.0
°
C)
OFF
OFF
ON
OFF
J (
−
100 to 850
°
C)
ON
OFF
ON
OFF
J (0.0 to 400.0
°
C)
OFF
ON
ON
OFF
T
ON
ON
ON
OFF
E
OFF
OFF
OFF
ON
L (
−
100 to 850
°
C)
ON
OFF
OFF
ON
L (0.0 to 400.0
°
C)
1
2
3
4
5
6
7
8
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...