104
Basic Specifications of Slave Units
Section 4-1
Note
When flashing, indicators are lit for 0.5 s and not lit for 0.5 s.
NS
Lit green.
Online and participating
Normal communications are in progress and the node is par-
ticipating in the network.
Flashing
green.
Online but not participat-
ing
Normal communications are in progress but the node is not
yet participating in the network.
Lit red.
Fatal communications
error
The address is set out of range.
The same address has been set for more than one node.
Flashing red.
Non-fatal communications
error
Polling has timed out. The network has timed out.
Not lit.
Power OFF/Baud rate not
yet detected.
The power supply is OFF or the baud rate has not been
detected.
Name
Indicator status
Node/communications
status
Meaning