458
Temperature Input Unit Functions
Section 11-5
Flag is turned ON, then enables the peak/bottom hold values after a fixed time
interval.
Setting Using CX-Integrator
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the tab for the input where peak/bottom hold is to be set, and select
the
Peak/Bottom
Check Box in the
Function Choice
Area.
4.
To allocate the Hold Flag (output) in the default connection path, click the
General
Tab Page and select
Holding Value
in the
Default Connection
Path (Out)
Field.
5.
Click the
Transfer [PC to Unit]
Button to download the data, and then click
the
Reset
Button to reset the Unit.
6.
Click the
OK
Button and exit the window.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...