301
Analog Input Slave Units
Section 6-4
Input Range and
Conversion Data
The analog data that is input can be converted to digital data according to the
input range, as described here. If the input exceeds the input range, the AD
conversion data will be fixed at the upper or low limit.
■
Input Range: 0 to 5 V
The voltage range 0 to 5 V corresponds to 0000 to 1770 hex (0 to 6,000). The
convertible data range is FED4 to 189C hex (
–
300 to 6,300). Negative volt-
ages are expressed as two’s complements (16 bits). When a disconnection
occurs, the data equivalent to 0 V input will be used (0000 hex).
■
Input Range:1 to 5 V
The voltage range 1 to 5 V corresponds to 0000 to 1770 hex (0 to 6,000). The
convertible data range is FED4 to 189C hex (
–
300 to 6,300). If the input volt-
age falls below the input range (input voltage less than 0.76 V), a disconnec-
tion is detected and the data is set to 7FFF hex.
■
Input Range: 0 to 10 V
The voltage range 0 to 10 V corresponds to 0000 to 1770 hex (0 to 6,000).
The convertible data range is FED4 to 189C hex (
–
300 to 6,300). Negative
voltages are expressed as two’s complements (16 bits). When a disconnec-
tion occurs, the data equivalent to 0 V input will be used (0000 hex).
189C (6300)
1770 (6000)
0000 (0)
0 V
FED4 (
−
300)
−
0.25 V
5 V 5.25 V
Conversion data
Hexadecimal (decimal)
Voltage
189C (6300)
1770 (6000)
FED4 (
−
300)
0000 (0)
1 V
0.8 V
5 V 5.2 V
7FFF
0.76 V
(Disconnection detected below 0.76 V.)
Conversion data
Hexadecimal (decimal)
Voltage
Clamped above 5.2 V.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...