Temperature Input Unit Functions
Section 11-5
Adjustment Procedure for the CRT1-TS04T
Adjustment Procedure
Use the following procedure to adjust the Temperature Input Units. Follow the
flowchart closely for proper adjustment.
Note
The only sensors that can be adjusted are ones that operate while the power
supply is ON. When adjusting for sensors that are not presently in use,
change the input type setting, toggle the power supply or reset the Unit from
the CX-Integrator, and perform the adjustment procedure from the beginning
of the flowchart.
No
Yes
No
Yes
Prepare the device that requires adjustment.
Connect the device that requires adjustment.
When performing upper/lower limit adjustment,
open end of the cold junction compensator to
disable it.
First
adjustment?
Turn ON the power to the associated system
devices. Wait at least 30 minutes for the CRT1-
TS04T’s internal temperature to stabilize.
This stabilization time is the time required
when the power is turned ON for the first time.
This step can be skipped when adjusting the
second and following inputs.
Refer to the Operating Manuals for the other
devices in the system for details on their
required stabilization times, if any.
Set the input's lower limit adjustment value.
Set the input's upper limit adjustment value.
Prepare to adjust the bias compensation.
Short the leads of the cold junction
compensator and wait at least 60 minutes for
the temperature to stabilize.
A cold junction compensator and
compensating conductor are required for the
thermocouple being adjusted.
Set the input's bias compensation.
Adjust other
inputs?
Test indication accuracy after adjustment.
End
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...