Word Slave Unit and Bit Slave Unit Functions
Section 11-3
4.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
5.
Click the
OK
Button and exit the window.
11-3-3 Error Prevention for Surge Current at Startup (Input Units Only)
Description
This function can be used to prevent reading inputs while the I/O power is
OFF and for 100 ms after the I/O power is turned ON (i.e., until the Slave Unit
stabilizes). It helps avoid input errors caused by inrush current from con-
nected devices when the I/O power supply is turned ON. This function is
enabled or disabled by the CX-Integrator or by explicit messages.
Settings Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the CompoNet Slave Unit.
2.
Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select
Parameters - Edit
from the pop-up menu.)
3.
Click the
IN
Tab, and select Enable for the
Sensor Power ON Delay
.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...