363
Industry Standard Sensor Connectors
Section 9-3
9-3
Industry Standard Sensor Connectors
9-3-1
Two-point Input Units
CRT1B-ID02S/CRT1B-ID02S-1
Input Section Specifications
Note
The current consumption is for Bit Slave Unit communications cur-
rent when all inputs are OFF, i.e., it does not include input device
current consumption. The communications power supply is also
used for the I/O power supply for sensors. Be sure to consider the
sensor current consumption and the number of sensors connected
in addition to the communications power. The power supply current
consumption is expressed by the following formula.
Communications power supply current consumption = Bit Slave
Unit communications current consu (Bit Slave Unit input
current
×
number of inputs used) + (sensor current consumption
×
number of sensors used)
Item
Specification
Model
CRT1B-ID02S
CRT1B-ID02S-1
I/O capacity
2 inputs
Internal I/O common
NPN
PNP
ON voltage
10.5 VDC min. (between each input
terminal and the V terminal)
10.5 VDC min. (between each input
terminal and the G terminal)
OFF voltage
5 VDC max. (between each input ter-
minal and the V terminal)
5 VDC max. (between each input ter-
minal and the G terminal)
OFF current
1.0 mA max.
Input current
3.0 mA min./input (at 10.5 VDC)
Sensor power supply voltage
Communications power supply voltage 0 V (max.)
Communications power supply voltage
−
1 V (min.)
ON delay
1.5 ms max.
OFF delay
1.5 ms max.
Number of circuits per com-
mon
2 inputs/common
Power short-circuit detection
Supported.
Isolation method
No isolation
Input indicators
LEDs (yellow)
Degree of protection
IEC standard IP20
Installation
Screw installation (M4)
Power supply type
Network power supply
Communications power sup-
ply current consumption (See
note.)
65 mA max. for 24-VDC power sup-
ply voltage
80 mA max. for 14-VDC power sup-
ply voltage
45 mA max. for 24-VDC power sup-
ply voltage
65 mA max. for 14-VDC power sup-
ply voltage
Weight
70 g max.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...