65
Connecting Cables and Terminating Resistor
Section 3-4
Installation Method
1,2,3...
1.
Attach the Open Type Connector to the communications connector of the
Slave Unit or Repeater Unit.
Orient the Open Type Connector so that the side with the open terminals
is facing to the left and press in the Open Type Connector until it clicks into
place.
Note
To remove the Open Type Connector once it has been attached,
firmly press in on the latches on both sides and pull out the Open
Type Connector.
2.
Open the terminal cover of the Open Type Connector and connect the ca-
ble wires to BDH (communications data high) and BDL (communications
data low) in the terminal block. For round cable II, connect the cable wires
to BS+ (communications power supply plus) and BS- (communications
power supply minus).
Note
Before connecting the cable wires to the terminal block, first attach the M3
crimp terminals shown below to the wires.
Connecting Flat
Cable I
A DCN4-BR4 Flat Connector Plug attached to a Communications Cable is
connected to the communications connector of a Slave Unit or Repeater Unit.
Installation Method
Be sure the face of the Connector on which line colors are indicated (red,
white, black, and blue) is facing to the left and press in the Connector until it
clicks into place.
Open Connector
M3 terminal block
Communications
connector
Slave Unit/Repeater Unit
MS NS
REMOTE TERMINAL
WORD NODE ADR
CRT1
CRT1-OD16
OD16-1
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
X10
[0-63]
X1
OUT
01
2
3
4567
8
9
01
2
3
4567
8
9
MS NS
REMOTE TERMINAL
WORD NODE ADR
CRT1
CRT1-OD16
OD16-1
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
X10
[0-63]
X1
OUT
01
2
3
4567
8
9
01
2
3
4567
8
9
6.0 mm max.
6.0 mm max.
Communications
connector
Slave Unit/Repeater Unit
Flat Connector Plug
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...