329
Status Areas
Section 7-3
7-3
Status Areas
A Temperature Input Unit has two status areas. The flags are turned ON and
OFF based on the threshold values set by the user for each function in that
Unit.
If any flag in a Status Area in the Slave Units connected to the Master Unit
turns ON, a corresponding status flag in the Master Unit turns ON. Bit 12 in
the Master Unit corresponds to the Warning Status Area and bit 13 corre-
sponds to the Alarm Status Area.
The Temperature Input Unit's status area information can be read by using the
CX-Integrator or explicit messages.
Warning Status Area
The Temperature Input Unit's Warning Status Area contains the following 16
bits. These bits indicate minor errors in the Unit.
Master Unit
The Master Unit has a Warning Status Bit and Alarm
Status Bit.
The status of each of these bits is an OR status of the
bits in the status area in the connected Slave Unit.
Transmitted to Master Unit
Temperature Input Unit
The Status Area in the Temperature Input
Unit has a Warning Status Area and an
Alarm Status Area.
Bit
Content
Description
0
Reserved.
Cannot be used.
1
Reserved.
Cannot be used.
2
Network Power Voltage Drop Flag
OFF: Normal
ON: Error (Voltage dropped below
threshold.)
Turns ON when the Network Power
Voltage drops below the voltage set as
the threshold for monitoring.
3
Unit Maintenance Flag
OFF: Normal
ON: Error (Threshold exceeded.)
Turns ON when the Total Unit Conduc-
tion Time exceeds the value set as the
threshold for monitoring.
4
Reserved.
Cannot be used.
5
Reserved.
Cannot be used.
6
Reserved.
Cannot be used.
7
Reserved.
Cannot be used.
8
Temperature Input Warning Flag
OFF: Within range (below set moni-
tor value)
ON: Out-of-range (equal to or above
set monitor value)
Turns ON when the temperature data
exceeds the displayable range or the
monitor value set for the comparator
function.
9
Cumulative Counter Exceeded Flag
OFF: Within range (below set moni-
tor value)
ON: Out-of-range (equal to or above
set monitor value)
Turns ON when the cumulative value
exceeds the set monitor value.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...