340
Temperature Input Units
Section 7-5
Note
1.
The display data will be clamped at the minimum value when the value is
below the minimum display value but higher than the value at which an off-
wire condition is detected.
2.
When an off-wire condition is detected, the display data will be 7FFF.
(In 1/100 Display Mode, the display data will be 7FFF FFFF.)
CRT1-TS04P Data Ranges
Note
1.
If the Unit is subjected to sudden temperature changes, moisture may con-
dense in the Unit and cause incorrect indications. If there is condensation,
remove the Unit from service and keep it at a steady temperature for about
1 hour before using it again.
2.
If the input temperature exceeds the convertible range, the temperature
data will be clamped at the minimum or maximum value.
If the temperature exceeds the convertible range by a certain value, an off-
wire condition (broken or disconnected input wire) will be detected and the
temperature data will be set to 7FFF Hex. If the input temperature returns
to the convertible range, the off-wire detection function will be reset auto-
matically and normal conversion data will be stored.
Terminal Arrangement
CRT1-TS04T
CRT1-TS04P
L (0.0 to
400.0
°
C)
−
20.0 to 420.0
FF38 to 1068
−
20.0 to 770.0
FF38 to 1E14
U
−
220.0 to 420.0
F768 to 1068
−
320.0 to 720.0
F380 to 1C20
N
−
220 to 1,320
FF24 to 0528
−
320 to 2,320
FEC0 to 0910
W
−
20 to 2,320
FFEC to 0910
−
20 to 4,120
FFEC to 1018
B
80 to 1,820
0050 to 071C
280 to 3,220
0118 to 0C94
PL2
−
20 to 1,320
FFEC to 0528
−
20 to 2,320
FFEC to 0910
Input type
°
C
Display
°
F
Display
Input type
°
C
Display
°
F
Display
PT100
(
−
200 to
850
°
C)
−
220.0 to 870.0
F768 to 21FC
−
320.0 to
1,520.0
F380 to 3B60
PT100
(
−
200 to
200
°
C)
−
220.0 to 220.0
F768 to 0898
−
320.0 to 400.0
F380 o 0FA0
NC
NC
NC
NC
NC
NC
NC
0
+
0
−
NC
1
+
1
−
2
+
2
−
3
+
3
−
Cold junction compensator
Adjusts the input temperature. Do not touch or remove
the compensator. The correct temperature data will not
be displayed if the compensator is disturbed.
NC
NC
NC
NC
2B
2B
3B
3B
3A
2A
NC
NC
0B
0B
1B
1B
1A
0A
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...