367
Industry Standard Sensor Connectors
Section 9-3
9-3-2
Two-point Output Units
CRT1B-OD02S/CRT1B-OD02S-1
Output Section Specifications
Note
The current consumption is for Bit Slave Unit communications cur-
rent when all outputs are OFF, i.e., it does not include the output de-
vice load current consumption. The communications power supply
is also used for the I/O power supply for actuators. Be sure to con-
sider the actuator load current consumption and the number of sen-
sors connected in addition to the communications power. The
power supply current consumption is expressed by the following
formula.
Communications power supply current consumption = Bit Slave
Unit communications current consu (actual load current
×
number of actuators used)
Item
Specification
Model
CRT1B-OD02S
CRT1B-OD02S-1
I/O capacity
2 outputs
Internal I/O common
NPN
PNP
Rated output current
0.2 A/output
Load power supply voltage
Communications power supply voltage 0 V (max.)
Communications power supply voltage
−
1.2 V (min.)
Residual voltage
1.2 V max. (0.2 A DC, between each
output terminal and BS
−
)
1.2 V max. (0.2 A DC, between each
output terminal and BS+)
Leakage current
0.1 mA max.
ON delay
0.5 ms max.
OFF delay
1.5 ms max.
Number of circuits per com-
mon
2 outputs/common
Load short-circuit detection
Supported.
Isolation method
No isolation
Output indicators
LEDs (yellow)
Degree of protection
IEC standard IP20
Installation
Screw installation (M4)
Power supply type
Network power supply
Communications power sup-
ply current consumption (See
note.)
55 mA max. for 24-VDC power supply
voltage
75 mA max. for 14-VDC power supply
voltage
55 mA max. for 24-VDC power supply
voltage
70 mA max. for 14-VDC power supply
voltage
Weight
59 g max.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...