453
Analog I/O Slave Unit Functions
Section 11-4
Setting Output Value
for Errors
The value that is output when communications errors (time-out and BusOff
errors) occur can be set for each output. The four output settings are set using
the CX-Integrator.
Setting Patterns
Output Ranges and Values
Note
When a node address has been used more than once or a Unit error has
occurred, the current output will be 0 mA and the voltage output will be 0 V,
regardless of the setting.
Setting Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the CompoNet Slave Unit.
2.
Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select
Parameters - Edit
from the pop-up menu.)
3.
Select the Tab Page for the output where the communications error output
value is to be set, and select the desired item from the pull-down menu in
the
Fault State
Field.
Low limit
Outputs the values in the following table according to the output range.
High limit
Outputs the values in the following table according to the output range.
Hold last state
Holds and outputs the value from immediately before the error occurred.
Zero count
Outputs the value when 0 is written from the Host. This setting will be
affected by scaling settings that are used.
Output range
Low limit
High limit
Hold last state
0 to 5 V
–0.25 V
5.25 V
Holds value.
1 to 5 V
0.8 V
5.2 V
Holds value.
0 to 10 V
–0.5 V
10.5 V
Holds value.
–10 to 10 V
–11 V
11 V
Holds value.
4 to 20 mA
3.2 mA
20.8 mA
Holds value.
0 to 20 mA
0 mA
21 mA
Holds value.
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...