437
Analog I/O Slave Unit Functions
Section 11-4
8.
Click the
OK
Button and exit the window.
Disconnected Line
Detection
When a disconnection occurs in an analog input line (voltage input or current
input), the Disconnected Line Detection Flag turns ON for each input that is
valid in the number of AD conversion points. The Disconnected Line Detection
Flags are included in the Analog Status Flags.
When Disconnected Line Detection is enabled, the value of AD conversion
data is set to 7FFF hex. When the input returns to a value within the range
that can be converted, the Disconnected Line Detection function will automat-
ically be turned OFF, and normal data conversion will occur.
Disconnected Line detection is supported for input ranges of 1 to 5 V or 4 to
20 mA only. With the 1 to 5 V input range, a disconnected line is detected
when the input voltage is below 0.76 V (less than 6%). With the 4 to 20 mA
input range, a disconnected line is detected when the input current is below
3.04 mA.
User Adjustment
Depending on factors such as the characteristics and connection methods of
the input device, the input can be adjusted to compensate for error in the input
voltage or current. The following diagram shows when compensation is
applied to the conversion line at the two points for 0% and 100%.
The following table shows the input ranges that support user adjustment.
Setting Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the CompoNet Slave Unit.
2.
Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select
Parameters - Edit
from the pop-up menu.)
3.
Select the Tab Page for the input to be adjusted, and click the
Adjustment
Button. (At this time, set the input range.)
Input range
Low Limit
High Limit
0 to 5 V
–0.25 to 0.25 V
4.75 to 5.25 V
1 to 5 V
0.8 to 1.2 V
4.8 to 5.2 V
0 to 10 V
–0.5 to 0.5 V
9.5 to 10.5 V
–10 to 10 V
–11 to –9.0 V
9.0 to 11 V
4 to 20 mA
3.2 to 4.8 mA
19.2 to 20.8 mA
0 to 20 mA
–1.0 to 1.0 mA
19 to 21 mA
100%
0%
Conversion data
After adjustment
Before adjustment
Voltage/current
Summary of Contents for CRT1 - 10-2008
Page 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 23: ...xxiv Conformance to EC Directives 6...
Page 51: ...28 Slave Unit Models Section 1 2...
Page 123: ...100 Connecting External I O for Slave Units Section 3 6...
Page 365: ...342 Temperature Input Units Section 7 5...
Page 381: ...358 Expansion Unit Specifications Section 8 2...
Page 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Page 419: ...396 Repeater Unit Section 10 2...
Page 424: ...401 CX Integrator Section 11 1...
Page 575: ...552 Current Consumption Summary Appendix D 552...
Page 581: ...558 Index...
Page 583: ...560 Revision History...