Trouble locating and clearing procedures (continued) 1-153
DMS-100 Family NA100 Trouble Locating and Clearing Procedures Volume 2 of 2 LET0015 and up
Replacing a cooling unit electronic module
CPC A0383326, A0383327, A0383984
(end)
At the front of the cabinet
18
Determine if power for the cooling unit connects through a PDC or a CPDC.
At the front of PDC
19
To insert the cooling unit fuses, push the fuse cartridges straight into the front
panel of the PDC.
Go to step 21.
At the front of CPDC
20
Throw the circuit breakers for the cooling unit.
At the front of the cabinet
21
Determine if all the cooling unit fans work.
Note: If one or more of the cooling unit fans does not work, the fan failure
lamp turns ON. The fan failure lamp is at the top of the cabinet between
the doors.
22
To reinstall the cooling unit cover, insert the mounting screws into the cover.
Note: Step 9 shows the location of the mounting screws.
23
Close the cabinet doors.
Go to step 25.
24
For additional help, contact the next level of support.
25
The procedure is complete.
If the power for the cooling unit
Do
connects through a PDC
step 19
connects through a CPDC
step 20
If
Do
all fans work
step 22
any fans do not work
step 24