1-208 Trouble locating and clearing procedures (continued)
297-8021-544 Standard 14.02 May 2001
Replacing a fan in a 42-in. cabinet
(continued)
Replacing a fan in a 42-in. cabinet
At your current Location
1
Obtain a replacement for the cooling unit fan.
At the front of the cabinet
2
Record the cabinet number.
Note: The cabinet number (for example D00) is on the front of the cabinet,
above the doors.
3
Consult office records or operating company personnel. Determine if power
to the cooling unit connects through a power distribution center (PDC) or a
cabinetized PDC (CPDC).
At the front of the PDC
4
Locate the cooling unit fuses.
Note: The cooling unit fuse cartridges are on the front panel of the PDC.
The fuse cartridges contain two cooling unit fuses. One fuse is for the side
A power feed and the other fuse for the side B power feed. The cabinet
number (recorded in step 2) is above each fuse cartridge. The letters SN
CU (SuperNode cooling unit) are below each fuse cartridge.
DANGER
Risk of injury or damage to equipment
When you replace a cooling unit, do not wear jewelry, (for
example, rings, bracelets or necklaces).
WARNING
Possible equipment damage
Do not remove power to the cooling unit for more than 30
minutes. Extended removal of power can cause the
equipment to overheat and cause damage.
If power to the cooling unit
Do
connects through a PDC
step 4
connects through a CPDC
step 6