1-86 Trouble locating and clearing procedures (continued)
297-8021-544 Standard 14.02 May 2001
Replacing a 3.5 in. disk drive unit
NTFX32BA
(continued)
7
Record the name and size (in blocks) of all disk volumes.
8
To test the DDU, type
>TST
and press Enter.
Example of a MAP display:
9
From the MAP response in step 8, record the location (floor, row, bay, and
shelf) of the replaced DDU.
10
Notify all users that there will be an interruption of service for the device. Wait
until all users stop use of the device before you proceed to the next step.
11
To manually busy the DDU, type
>BSY
and press Enter.
Example of a MAP display:
12
To manually stop the DDU, type
>STOP
are not present
step 7
If the test
Do
passes
step 32
fails
step 9
If the BSY command
Do
passed
step 12
failed
step 38
If open files
Do
Process may take up to 3 min
Failed
Drive is disconnected
.
Site Flr RPos Bay–Id Shf Description Slot EqPec
HOST 01 A00 ISME 03 32 IOC 0 DDU 04
FX30AA
HOST 01 A00 ISME 03 32 IOC 0 DDU 04
FX31AA
bsy
OK