5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.5 Temperature Controller Side Setting
5 - 15
1
P
R
EP
ARA
T
OR
Y
P
R
OCEDURES
FOR
MONIT
O
R
ING
2
C
O
NNECTION T
O
IAI
ROBO
T
CO
N
T
RO
L
L
E
R
3
CONNECTION T
O
AZBI
L C
O
NTR
O
L
EQUI
PMENT
4
CONNECTION T
O
OMRON PLC
5
CONNECTI
O
N T
O
OMRO
N TEMPERA
TURE
CONTROL
LE
R
6
CONNECTION T
O
KE
YENCE PL
C
7
CONNE
C
T
ION T
O
KO
YO
EI
PLC
8
CONN
E
CT
ION T
O
JT
EK
T PL
C
(2) Settings of data length, parity bit, stop bit, master/
slave device and echoback
5.5.4
Station No. settings
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
(1) Direct specification
When setting the device, specify the station number of
the temperature controller of which data is to be
changed.
(2) Indirect specification
When setting the device, indirectly specify the station
number of the temperature controller of which data is to
be changed using the 16-bit GOT internal data register
(GD10 to GD25).
When specifying the station No. from 100 to 115 on GT
Designer3, the value of GD10 to GD25 compatible to
the station No. specification will be the station No. of
the temperature controller.
(3) All station specification
Target station differs depending on write-in operation or
read-out operation.
• For write-in operation, all station will be a target.
• For read-out operation, only one station will be a
target.
Setting
item
Set value
Switch No.
4
5
6
7
8
9
0
Data bit
7bits
OFF
8bits
ON
Stop bit
2bits
OFF
1bit
ON
Parity
Even
OFF OFF
Odd
ON OFF
None
OFF ON
Commun
ication
Type
RS232
RS422
OFF ON
RS-232
RS485
OFF OFF
Echo
back
Without
OFF
With
ON
ON
SW
Set these switches.
Model name
Specification
range
E5AN, E5EN, E5CN, E5GN
0 to 99
E5ZN
0 to 15
Specification
station NO.
Compatible
device
Setting range
100
GD10
0 to 99: For E5AN, E5EN, E5CN or E5GN
0 to 15: For E5ZN
For the setting other than the above, error
(dedicated device is out of range) will
occur.
101
GD11
102
GD12
103
GD13
104
GD14
105
GD15
106
GD16
107
GD17
108
GD18
109
GD19
110
GD20
111
GD21
112
GD22
113
GD23
114
GD24
115
GD25
GOT
Station
No.3
Station
No.7
Station
No.1
Station
No.15
Station
No.6
Examples of station number setting
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......