3 - 36
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.3 Connection Diagram
RS485 connection diagram 21)
*1
Set the terminating resistor selector of the GOT main unit to "110
Ω
".
■
Connecting terminating resistors
*2
Connect FG grounding to the single-sided end of a cable shield line.
RS485 connection diagram 22)
*1
Set the 2-wire/4-wire terminating resistor setting switch of the RS-232/485 signal conversion adaptor as follows.
2-wire type/4-wire type : 2-wire type (1Pair)
Terminating resistor
: 110
Ω
1.4.4 Setting the RS-232/485 signal conversion adaptor
*2
Connect FG grounding to the single-sided end of a cable shield line.
GOT side
*1
*2
Temperature controller side
plug RJ-11 for 4-pin modular jack
Fixed side
socket pin assign
SG
DB
DA
(Recognition pin)
DMC50
SDA
SDB
RDA
RDB
SG
RSA
CSA
RSB
CSB
1
6
2
7
5
3
4
8
9
DA
DB
SG
Recognition pin
GOT side
*1
*2
Temperature controller side
plug RJ-11 for 4-pin modular jack
Fixed side
socket pin assign
SG
DB
DA
(Recognition pin)
DMC50
SDA
SDB
RDA
RDB
SG
DA
DB
SG
Recognition pin
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......