10.5 Indicating Controller Side Setting
POINT
POINT
POINT
(1) Shinko Technos indicating controller
For details of Shinko Technos indicating controller,
refer to the following manual.
User's Manual of the Shinko Technos indicating
controller
(2) Communication converter
For details on communication settings of the
communication converter, refer to the following
manual.
User's Manual of communication converter
10.5.1 Connecting to ACS-13A, DCL-
33A, JC, JCM-33A, JIR-301-
M, PCD-300 Series, PC-900
Series (PC-955-[ ]/M,C5, PC-
935-[ ]/M,C5)
Communication settings
Make the communication settings by operating the key
of the indicating controller.
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
*3
When setting the "95" to the station No., the read-out of data
cannot be performed.
10.5.2 Connecting to FCD-100, FCR-
100, FCR-23A, FIR Series,
PC-900 Series (PC-955-[ ]/
M,C, PC-935-[ ]/M,C)
Communication settings
Make the communication settings by operating the key
of the indicating controller.
*1
Adjust the settings with GOT settings.
*2
When setting the "95" to the station No., the read-out of data
cannot be performed.
10.5.3 Connecting to communication
converter (IF-400)
Communication settings
Make the communication settings by operating the key
of the communication converter.
*1
Adjust the settings with GOT and the indicating controller
settings.
*2
The setting of 1 character is recommended.
Model name
Refer to
Indicating
controller
ACS-13A, DCL-33A, JC,
JCM-33A, JIR-301-M, PCD-300 Series,
PC-900 Series (PC-955- /M,C5, PC-
935- /M,C5)
FCD-100, FCR-100, FCR-23A,
FIR Series, PC-900 Series (PC-955- /
M,C, PC-935- /M,C)
Communication
converter
IF-400
Item
Set value
Transmission speed
*1
9600bps, 19200bps
Data bit
7bits (Fixed)
Parity bit
Even (fixed)
Stop bit
1bit (Fixed)
Station No.
*2*3
0 to 95
Communication protocol
Shinko protocol
Item
Set value
Transmission speed
*1
9600bps, 19200bps
Data bit
7bits (Fixed)
Parity bit
Even (fixed)
Stop bit
1bit (Fixed)
Station No.
*1*2
0 to 95
Communication protocol
Shinko protocol
Item
Set value
Transmission speed
*1
9600bps, 19200bps
Sending/Receiving
switching period
*2
1 character, 2 character
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......