background image

 

Product overview

What’s in the sensor box

     Tools you may need

 

Step ladder

 

Drill

 

Pencil

  

 

Pliers

What’s in the switch box

Install the switch

black

brass

ground

white

red

load

120-277 V~
50 / 60 Hz

hot/live

neutral

Switch

  WARNING: 

Wiring the device with power 

ON could result in serious injury or death.

1

 Remove power from the mains at fuse or circuit 

breaker. 

2

 Remove the old switch, if needed.

3

 Connect the wires according to the wiring diagram 

above. 

 

Note: Hot/live and neutral may not be swapped.

black

brass

ground

white

red

hot/live

neutral

120-277 V~
50 / 60 Hz

Three-way slave switch

4

 For a three-way circuit connect the wires as  

follows:

T

 

he master switch (that controls the load) 

according to the regular wiring diagram.
The

 

 slave switch (no load) according to the 

wiring diagram above. Make sure that the switch 
has a steady feed (hot/live and neutral). 

The three-way configuration is done via the 
menu, later in the installation. 

PHILIPS

PHILIPS

Multigang wall box

break

PHI

LIPS

PHI

LIPS

PHI

LIPS

PHI

LIPS

5

 

If installing in a multigang wall box: break the tabs 

of joining sides. Do not break the outside tabs on 
controls at the end of the gang.

PHILIPS

6

 Place the switch into the wall box, and fix it with the 

mounting bolts.

7

 Power the mains at fuse or circuit breaker.

PHI

LIP

S

ON

OFF

8

 Test that the switch is wired correctly using the  

rocker to turn the lights ON/OFF.

PHI

LIP

S

Attach a wall plate adapter and wall plate. Wall 

plate and adapter must be purchased separately. 

FCC and IC Regulations

 

This device complies with Part 15 of the FCC Rules and RSS-Gen of IC Rules. 
Operation is subject to the following two conditions : 
(1) this device may not cause harmful interference, and 
(2) this device must accept any interference received, including interference that may cause 
undesired operation. 
FCC WARNING: Changes or modifications not expressly approved by Philips Lighting 
Electronics N.A. could void the user’s authority to operate the equipment. This product is 
intended for commercial use only.

 

Co-location : This transmitter must not be co-located or operated in 
conjunction with any other antenna or transmitter.

  

CAUTION : Radio Frequency Radiation Exposure 
This equipment complies with FCC radiation exposure limits set forth for 
uncontrolled equipment and meets the FCC radio frequency (RF) Exposure 
Guidelines in Supplement C to OET65. This equipment has very low levels of 
RF energy that it deemed to comply without maximum permissive exposure 
evaluation (MPE). But it is desirable that it should be installed and operated with 
at least 20cm and more between the radiator and person’s body (excluding 
extremities: hands, wrists, feet and ankles). 

Copyright NOTICE

All referenced brands, product names, service names and trademarks are the property 
of their respective owners. Copyright 2009 Koninklijke Philips Electronics N.V. 

TECHNICAL SUPPORT

For technical support on this product, please contact:
Philips Lighting Electronics N.A.
10275 W. Higgins Road
Rosemont IL 60018
Customer Care: 

1-800-372-3331 

[email protected]

PHILIPS

PHILIP

S

Sensor unit

Link button

Switch

Mounting frame

Side tabs

Wires

Retractable, rotatable

shield

Link button

”Traffic light”

indicator LEDs
Rocker

Menu button

Movement detector

Indicator LEDs

Mounting plate

Movement detector (”sensor”)

Wall switch (”switch”)

Screwdrivers 
(small & large)

Install the sensor

30

1

1

 Set the dial on the sensor to 1 minute for testing 

purposes.

2

 Place the battery into the sensor.

CAUTION: 

Only use a high-quality 3.6V lithium-

thionyl chloride battery with the sensor. 
See 

SAFETY

 for more information on the battery.

23.6ft (7.2m)

17.7ft (5.4m)

17.7ft (5.4m)

11.8ft (3.6m)

h= 8ft (2.4m)

Large movements

Small movements

3

 Choose the sensor location on the ceiling.  

The 

window arrow

 in the mounting plate defines 

the direction of the detection field, which is 
rectangular. See 

Sensor placement guidelines

 for 

more information.

Sensor placement guidelines

The sensor should be mounted in such a way that:

• 

  Small movements are detected for the workspace

  Large movements are detected for the entire room,  

and in particular for the area near the doorway.

  Motion from adjectent areas, e.g. the hallway, is not 

picked up.

The

 

 center of a room is usually not a good location. 

Moving the sensor towards the wall where the door is 
located may still cover the entire room, while blocking 
unwanted detection of motion from the hallway.
The sen

• 

sor should not be placed close to heat 

sources (especially incandescent lamps) or HVAC 
exhausts.

4

 Fix the mounting plate onto the sensor‘s location, 

using the mounting hardware.  Alternatively, use 
toggle bolts (not included).

PHILIP

S

5

 Place the sensor onto the mounting plate, and rotate 

clockwise to fix.

6

 If needed, pull out the sensor shield (indicated on the 

ring with a dot), and rotate it to the required direction. 
This step is covered in more detail in 

Configure, test 

& finish.

PHILIPS

(1x)

(1x)

(1x)

+

_

(2x)

(2x)

(2x)

(4x)

(1x)

(1x)

PHILIPS

(2x)

1

2

3

4

EN

PHILIPS

PHILIPS

Install the switch 

Install the sensor 

Link devices

Configure, test & finish

Product description  

OccuSwitch

TM 

Wireless is a system for automatically controlling 

the lights based on occupancy.  The system uses two parts: a 
ceiling-mounted sensor and a switch. The switch will turn the 
lights on and off based on the information it wirelessly gets from 
the battery-powered sensor.

Key figures

Sensor coverage area

Will vary based on ceiling height  
(up to 12ft).  
For a typical height of 8ft (2.4m): 
Large motion 17.7 x 23.6ft (5.40m x 7.20m)
Small motion 11.8 x 17.7ft (3.60m x 5.40m)
Larger areas will require multiple sensors. 

Wireless range

Switch - sensor: 50ft (17m) 
Switch - switch (same plane): 18ft (6m) 
Switch - switch (line of sight): 50ft (17m)

Maximum network size

10 Sensors/switches (any combination)

Operating voltage

120V AC or 277V AC, 60Hz

Load  
rating: 

Electronic 
Fluorescent Ballast

120V / 10.8A / 1300VA 
277V / 4.7A / 1300VA

Electromagnetic 
Fluorescent Ballast

120V / 10.8A / 1300VA 
277V / 4.7A / 1300VA

Incandescent lamps 120V / 6.67A / 800W
Motor load

120V / 0.25HP

Sensor dimensions   
(diameter x height)

3.3 x 0.98 in (84 x 25mm)

Battery

Lithium-thionyl chloride, AA 3.6V DC

Switch dimensions  
(l x w x d)

4.13 x 2.56 x 1.79 in (105 x 65 x 45mm)

Minimum wall box depth 2.5 in
Operating conditions: 
temperature

41°F - 104°F (5°C – 40°C)

Operating conditions: 
humidity

20% – 85%, non-condensing

SAFETY

Parts of the switch carry mains power, which is a potential lethal 

voltage. This product was designed and manufactured to ensure 

maximum safety during operation and service.  Always read these 

safety instructions before installing, maintaining or servicing the 

product, and strictly comply with these instructions.

General

- If you are unsure about any part of these installation 

instructions, consult a qualified electrician.

- The devices are designed for indoor use only.  

Do not expose the product to rain or moisture, to avoid short 

circuit. Short circuit may cause fire or electric shock hazard. 

Operate the devices between 41°F and 104°F (5°C and 40°C).

- Use only a soft damp cloth to clean devices, never use any 

abrasive or chemical cleaner.

- Whenever it is suspected that safety protection is impaired, 

the product must be made inoperative and secured against 

unintended operation. The device must be serviced or 

replaced as soon as possible. Safety is likely to be impaired 

if, for example, the equipment fails to perform the intended 

functions or if the equipment shows visible damage.

- Do not paint the devices.

Switch only

- Disconnect power at circuit breaker or fuse when servicing, 

installing or removing the fixture of the switch.

- Use the switch only with copper or copper clad wire.

- Connect the switch to the power mains according to the 

wiring scheme in this manual. 

Sensor only

- The sensor cannot be used to control any load, without a 

compatible switch.

- Use only high-quality 3.6V lithium-thionyl chloride batteries 

with the sensor: one (1) Lithium-thionyl chloride (AA, 3.6V). 

Using improperly rated batteries may damage the sensor. 

- Dispose of used batteries promptly. Keep batteries away from 

children, do not disassemble and do not dispose of in fire.

  WARNING: 

This product must not be used to 

control equipment that could create hazardous situations when 
operated accidentally, like entrapment. Examples of equipment 
that must not be controlled with this product include (but are 
not limited to) motorized gates, garage doors, industrial doors, 
(microwave) ovens, heating devices etc. 

  WARNING: 

It is the installer’s responsibility to 

ensure that the equipment being controlled is visible from every 
control location and that only suitable equipment is connected 
to these controls. Failure to do so could result in serious injury 
or death.

CAUTION: 

The battery used with the sensor device may 

present a risk of fire or chemical burn if mistreated. Do not 
recharge, disassemble, heat above 100°C, or incinerate.  Replace 
battery with Lithium-thionyl chloride (AA 3.6V) only.  
Use of another battery may present a risk of fire or explosion.

OccuSwitch

TM

 Wireless

Installation guide

PA-7200-R01 08-09

Installation steps:

Reviews: