5 - 16
5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.6 Device Range that Can Be Set
5.6 Device Range that Can Be Set
The device ranges of controller that can be used for GOT
are as follows.
Note that the device ranges in the following tables are the
maximum values that can be set in GT Designer3.
The device specifications of controllers may differ
depending on the models, even though belonging to the
same series.
Please make the setting according to the specifications of
the controller actually used.
When a non-existent device or a device number outside
the range is set, other objects with correct device settings
may not be monitored.
Setting item
*1
The following table shows the relation between station
numbers of the PLC and the GOT data register.
POINT
POINT
POINT
Device settings of OMRON temperature controller
(1) When setting the (S)
Make settings for status by a channel number and
a bit position.
(2) When setting variable area (0), variable area (1)
and variable area (2)
Make setting for variable areas by a channel
number and address.
5.6.1
OMRON temperature
controller (OMRON
THERMAC/INPANEL NEO)
*1
Only reading is possible.
*2
Only writing is possible.
Numerical input cannot be used.
When writing, use [Word Set] of a data set switch.
*3
Only 32-bit (2-word) designation is allowed.
Item
Description
Device
Set the device name, device number, and bit number.
The bit number can be set only when specifying the bit of
word device.
Information
Displays the device type and setting range which are
selected in [Device].
Network
Set the monitor target of the set device.
All
Select this item when writing data to all
temperature connected.
During monitoring, the temperature controller of
station No.0 is monitored.
(When writing the data in numerical input, the
data is written to all connected temperature
controllers during input, and the temperature
controller of station No. 0 is monitored during
other than input (displaying).)
Station
No.
Select this item when monitoring the temperature
controller of the specified station No.
After selecting, set the station No. in the following
range.
0 to 99:
To monitor the temperature
controller of the specified station
No.
100 to 115:
To specify the station No. of the
temperature controller to be
monitored by the value of GOT
data register (GD).
*1
Station
No.
GOT data register
(GD)
Setting range
100
GD10
0 to 99
(If setting a value outside
the range above, a
device range error
occurs.)
101
GD11
:
:
114
GD24
115
GD25
Device name
Setting range
Device No.
representation
B
it de
vi
ce
Status (S)
*1
S0000 to S0031
S0100 to S0131
Decimal
Wo
rd
d
ev
ic
e
Operation command
(A)
*2
A0000 to A000C
Hexadecimal
Variable area 0
(C0)
*1*3
C00000 to C00006
C00100 to C00106
D
Hexadecimal
Variable area 1
(C1)
*3
C10000 to C1001C
C10100 to C1011C
Variable area 3
(C3)
*3
C30000 to C3003E
C30100 to C3013E
Bit position
Channel No.
Address
Channel No.
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......