11 - 30
11. CONNECTION TO CHINO CONTROLLER
11.5 Controller Side Setting
11.5.10 Connecting to KE3000
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting.
Communication settings
Make the communication settings by operating the
switches SW2 and SW3 of the module.
(1) Setting by SW2
*1
Adjust the settings with GOT settings.
*2
When the transmission code is MODBUS RTU, the setting of
the transmission character structure is fixed.
(2) Setting by SW3
Set the station No. as follows.
*1
Avoid duplication of the station No. with any of the other
units.
11.5.11 Connecting to LE5000
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting.
Communication settings
Set the communication settings with controller key
operation.
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
Item
Set value
SW2-2
SW2-3
Transmission code
*2
MODBUS RTU
OFF
-
Transmission speed
*1
9600bps
-
OFF
19200bps
-
ON
Transmission character
structure
*2
8bits, None, 1bit (fixed)
-
-
SW3-4
SW3-5
SW3-6
SW3-7
SW3-8
Station No.
*1
OFF
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
OFF
1
OFF
ON
OFF
OFF
OFF
2
ON
ON
OFF
OFF
OFF
3
:
:
ON
OFF
ON
ON
ON
29
OFF
ON
ON
ON
ON
30
ON
ON
ON
ON
ON
31
Printed wiring board
in main body
Front panel
SW3 SW2
Item
Set value
RTU/ASCII
RTU
Station No.
*1
1 to 99
Transmission speed
*2
9600bps, 19200bps
Character
*2
(Bit length, Parity bit, Stop bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......