background image

Funktionsbeschreibung

Operational description

Description de fonctionnement

Descripción de funcionamiento

TST-2

TST WS-B /

 

021016

D

GB

F

NL

Summary of Contents for GAROG TST WS Series

Page 1: ...Funktionsbeschreibung Operational description Description de fonctionnement Descripción de funcionamiento TST 2 TST WS B 021016 D GB F NL ...

Page 2: ...Funktionsbeschreibung Operational description Description de fonctionnement Descripción de funcionamiento TST 2 TST WS B 021016 D GB F NL ...

Page 3: ... customer and may not be transferred The warranty promise comprises only those products delivered by Chamberlain GmbH We are non liable for the whole system Instructions to Software Chamberlain GmbH reserves the right to alter or extend its software without prior notice as long as functionality remains untouched resp is adjustable Before applying individual software the correctness of the software...

Page 4: ...ing light L3 change over contact N External supply 2 24VDC 500mA regulated Opening Potential free via contactor Closing Potential free via contactor Fault door position traffic light function 2x potential free change over contact Impulse series control single channel Pre warning before opening Run time supervision Relay functions optional plug in module Safety edge evaluation for door opening and ...

Page 5: ...on for the first time it must be en sured that all insert cards are correctly placed in the insertion spaces provided for them When the door is moving in deadman operation it is to be ensured that the door region can be seen by the operator since in this type of operation security devices such as the security strip and light barriers can be bypassed The manual operation of the contactors is prohib...

Page 6: ...used The supply inlet is to be secured at the installation site with 16A actuation feature K The drives are to be fitted with additional over load protection eg thermoplate If the voltage free contacts of the relay outputs or other terminal clamps are connected to a external supply that means they have a dangerous voltage which can be active after switch off of the control ore disconnecting of the...

Page 7: ...lose ext 1 51 52 55 57 Three function push button 1 STOP 1 no travel possible OPEN automatic opening travel no deadman function DIP 2 CLOSE automatic closing travel no deadman function Opening device 2 Closing device Closing device Stop ext 2 Open ext 2 Close ext 2 53 54 56 58 Three function push button 2 STOP 1 no travel possible OPEN automatic opening travel no deadman function DIP 2 CLOSE autom...

Page 8: ... position 7 If the door turns in the wrong direction incorrect motor rotary field shut off the power and exchange two motor connections 8 Set the lower end switch such that it is just actuated Then adjust the end switches more precisely as required by further movements into this end position NB End switches must not be passed over in the end positions 9 Set lower security end switch Observe the se...

Page 9: ...security strip are in upper end position intermediate holding is not yet engaged broken Yard light Yard light actuating pulse 1s pulse before each commencement of travel to actuate an automatic staircase device Jumper JP400 Security strip Terminating resistor of the security strip 1 2 1 2kΩ 2 3 8 2kΩ 7 2 Setting of the hold open time trimmer P1 It effects the automatic closing travel of the door a...

Page 10: ...ED Fig 8 3 Output of the counter readingson the LEDs Run green SiLei orange NotSt red Inkr green Pulse number flashing x10000 Pulse number flashing x1000 Pulse number flashing x100 Pulse number flashing x10 Example A door cycle counter reading maintenance cycle counter reading of 63856 is displayed in the following sequence 6x flashes of the Run LED 6 x 10000 60000 3x flashes of the Sec Strip LED ...

Page 11: ...ng travel as stop command As long as actuation is set only deadman travel is possible After release automatic opening travel 2s delay takes place as far as the corresponding previously requested end position intermediate holding upper end position A hold open time which may have been set begins to run DIP 5 Pre warning OFF inactive Warning light relay K1 flashes only during opening and closing tra...

Page 12: ...ulty DIP6 ON eg pneumatic strip Redundancy faulty DIP6 OFF eg electrical strip Redundancy of plug in card for security strip faulty slip door operation Plug in card for security strip will not be recognised anymore Pulse rate in Fraba evaluation too high Plug card security strip permanent actuated OFF No error strip operates correctly eg suitable terminating resistor recognised red EMERG STOP Emer...

Page 13: ...e wheeling diodes and appropriate fault clearing measures Relay K1 warning light red light 230 VAC min 0 1 A max 80W L1 switching closing device Relay K2 fault yard light 24 VDC 500 mA 230 VAC min 0 1 A max 80W switching in a potential free manner change over contact contacts used one time for a switch of power current can not be uses anymore for low currents Auxiliary contacts on contactor openin...

Page 14: ... external Pull Down resistor of max 2 2kΩ from clamp 63 67 to clamp 64 68 draw in security not connected draw in security connected reflex light barrier draw in security connected one way light barrier channel 1 INSIDE 24V IN7 EO Test GND wire bridge 61 62 63 64 transmitter receiver module IN7 EO Test GND PNP 61 62 63 64 reflector 24V 24V signal test GND transmitter IN7 EO Test GND PNP 61 62 63 64...

Page 15: ... N 2 L B 31 32 Activation partial open ON OFF 14 11 13 16 12 Bridge for partial open 9 3 Appendix C Wiring of motor and end switches connection example 2 31 Relay K2 Relay K3 3 x 400VAC L1 L2 L3 N PE 82 83 84 85 86 91 92 93 94 95 96 97 98 40 41 42 43 44 32 33 34 35 36 37 38 11 12 13 PE N N N N 2 L X13 X10 A2 A2 14 T3 T2 T1 A1 13 L1 L2 L3 T1 F300 1 AT Open Relay K1 open 5 3 M 1 2 3 PE 10 11 4 9 5 4...

Page 16: ...ocontroller Emergency off switch Programming pin edge 1 Foil key X16 ON 1 2 3 4 5 6 7 8 Terminal box on door leaf slack rope switch Spiral cable ceiling pull switch pulse series command light barrier for object protection 24V 8k2 security strip matching resistor optional slip door switch electrical strip DIP6 OFF JP400 2 3 1k2 security strip matching resistor pneumatic strip DIP6 ON JP400 1 2 Rece...

Page 17: ...t Intermediate stop Pre end switch security strip End sw CLOSE End switch OPEN optional connection for plug in modules X11 X12 Connection for security strip internal module slack rope switch slip door emer end switch thermo contact Alarm lamp programming pin edge 1 foil key L Brake W Motor V Motor U Motor AC DC Brake L Brake 4x2 terminal bases Draw in security device 2 see clamping plan Draw in se...

Reviews: