11 - 28
11. CONNECTION TO CHINO CONTROLLER
11.5 Controller Side Setting
11.5.4 Connecting to DB1000,
DB2000 Series
Communication settings
Set the communication settings with controller key
operation.
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
11.5.5 Connecting to GT120 Series
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting to Lock 3.
Communication settings
Release the controller lock function in advance and set
the following communication settings.
After completing the communication settings, set the
Key Lock setting to Lock 3.
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
11.5.6 Connecting to KP1000,
KP2000
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting.
Communication settings
Set the communication settings with controller key
operation.
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
11.5.7 Connecting to AL3000,
AH3000
Key Lock setting
To write the Digital and the Analog parameters, set the
Key Lock setting.
Communication settings
Set the communication settings with controller key
operation.
*1
Avoid duplication of the station No. with any of the other
units.
*2
Adjust the settings with GOT settings.
Item
Set value
Protocol
MODBUS (RTU)
Function
Com: Upper communication
Station No.
*1
01 to 99
Transmission speed
*2
9600bps, 19200bps, 38400bps
Character
7BIT/EVEN/STOP1
7BIT/EVEN/STOP2
7BIT/ODD/STOP1
7BIT/ODD/STOP2
8BIT/NON/STOP1
8BIT/NON/STOP2
8BIT/EVEN/STOP1
8BIT/EVEN/STOP2
8BIT/ODD/STOP1
8BIT/ODD/STOP2
Item
Set value
Communication protocol
comr: MODBUS RTU
Station No.
*1
1 to 95
Transmission speed
*2
96: 9600bps
192: 19200bps
Data bit
8bits (fixed)
Stop bit
*2
1bit, 2bits
Parity bit
*2
nonE: None
EVEn: Even
odd: Odd
Item
Set value
Protocol
MODBUS (RTU)
Function
COM
Station No.
*1
1 to 99
Transmission speed
*2
2400bps, 4800bps, 9600bps,
19200bps, 38400bps
Character
*2
(Bit length, Parity bit, Stop bit)
8BIT/NON/STOP1
8BIT/NON/STOP2
8BIT/EVEN/STOP1
8BIT/EVEN/STOP2
8BIT/ODD/STOP1
8BIT/ODD/STOP2
Item
Set value
Protocol
MODBUS
Transmission code
rtu
Communication type
RS232C, RS-422A, RS-485
Station No.
*1
1 to 31
Transmission speed
*2
2400bps, 4800bps, 9600bps,
19200bps
Character
*2
(Bit length, Parity bit, Stop bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......