10. CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER
10.3 Connection Diagram
10 - 9
9
CONN
E
C
TION
T
O
S
H
ARP PLC
10
C
O
NN
ECTI
ON
T
O
SHI
N
KO
TECHN
OS IN
DIC
ATI
NG
C
O
NT
ROLLE
R
11
CONNECTION T
O
CH
INO
CONTROLLE
R
12
CONNECTION T
O
T
O
SHI
B
A
PL
C
13
CONNECTION T
O
T
O
SH
IB
A M
A
C
H
IN
E
PLC
14
CONNECTION T
O
P
A
NA
SONIC S
E
R
V
O
A
M
PL
IF
IE
R
15
CONNE
CTION T
O
PA
NA
SONIC
INDUSTRI
AL
DE
VI
CES
SU
NX
PLC
RS485 connection diagram 6)
*1
Pin No. of communication converter differs depending on the model. Refer to the following table.
*2
Connect FG grounding to the appropriate part of a cable shield line.
*3
For details of the terminating resistor specifications, refer to the following manual.
User's Manual of the Shinko Technos indicating controller
*4
Set the terminating resistor of GOT side which will be a terminal.
■
Connecting terminating resistors
GOT side
*4
YA(-)
YB(+)
SG
YA(-)
YB(+)
SG
8
6
2
1
3
4
5
7
9
10
11
12
13
14
15
16
17
18
19
20
Indicating
controller side
Indicating
controller side
*2
*2
Terminating resistor*
*3
SDB1(TXD1-)
SDA1(TXD1+)
SG
NC
NC
NC
SDA2(TXD2+)
SDB2(TXD2-)
RDA2(RXD2+)
RDA1(RXD1+)
RDB2(RXD2-)
RDB1(RXD1-)
NC
RSA(RTS+)
NC
RSB(RTS-)
NC
CSA(CTS+)
NC
CSB(CTS-)
Signal
name
Model of indicating controller
JCS-33A
JCR-33A
JCD-33A
JCM-33A
JIR-301-M
ACS-13A
PCD-33A
PC-955
PC-935
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
Pin No.
YA(-)
13
11
11
10
11
16
11
11
11
YB(+)
14
14
14
13
14
17
14
12
12
SG
15
17
17
14
17
18
17
16
16
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......