4 - 26
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
(3) Setting on the CP1H, CP1L
(4) Setting on the CP1E
Settings by DIP switch are not required.
Setting PLC system settings
(1) CJ1, CJ2, CS1
Make the PLC system settings.
*1
Only transmission speeds available on the GOT side are
shown.
*2
Set the same port transmission speed as that of the GOT
side.
*3
Set the host link station No. according to the Host Address
on the GOT side.
HINT
HINT
HINT
Precautions for changing the PLC system settings
Before changing the PLC system settings, make sure
that the switch settings have been changed as follows:
CJ1, CJ2, CS1: Front panel DIP switch SW5 to "OFF"
Switch
Description
Settings
SW4
Option
Board
Slot1
According
to PLC
Setup.
OFF
SW5
Option
Board
Slot2
OFF
Dip switch
1 2 3 4
5 6
ON
Channel
Bit
Item
Set value
160
15
Arbitrary
settings ON/
OFF
1
H
: Arbitrary settings
(fixed)
8 to 11
Serial
communication
mode
0
H
: Upper link (fixed)
3
Data bit
0
H
: 7bits (fixed)
2
Stop bit
0
H
: 2bits (fixed)
0 to 1
Parity
0
H
: Even (fixed)
161
0 to 7
Port
transmission
speed
*1*2
00
H
: 9600bps
05
H
: 4800bps
06
H
: 9600bps
07
H
: 19200bps
08
H
: 38400bps
09
H
: 57600bps
0A
H
: 115200bps
163
0 to 7
Host link station
No.
*3
0
H
to 1F
H
: No.00 to 31
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......