GOT-F900 SERIES (CONNECTION)
Connection of SYSMAC C Series PLC (Manufactured by Omron) 15
15-30
2) Software
Contents of trouble
Check points and countermeasures
Screen
creation
software
Communication with the screen
creation software and screen data
cannot be transferred.
A SYSMAC C Series PLC, bar code reader or printer is
connected.
• Causes
The RS-232C connector to which the personal computer is
connected is set to be used for another piece of equipment.
• Countermeasures
In the GOT-F900, select by hand "SELECT MODE"-"OTHER
MODE"-"DATA TRANSFER".
Or set a bar code reader to invalid and a printer to "DON'T
USE".
Something is wrong with the cable between the GOT-F900
and the personal computer.
• Causes
The connected cable is not proper. Or cable connection is
not correct.
• Countermeasures
Check the cable.
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......