GOT-F900 SERIES (CONNECTION)
Connection of MELSEC-Q Series PLC 11
11-30
"DATA IS NOT
FOUND." is
displayed on the
GOT-F900 screen.
There is not data because the unit is new or the
memory clear has been executed.
• Cause
There is no screen data.
• Countermeasures
Write the screen data using the screen creation
software.
−
Earlier
than
6.00
Earlier
than
4.00
−
A device that does not exist in the Q Series PLC was
referenced.
• Cause
On the head screen, a nonexistent device in the
connected Q Series PLC is specified.
(The head screen is the screen No. 1 in the GT
Designer, and the screen No. 0 in the DU/WIN.)
• Countermeasures
Check the devices used on the head screen.
While the Q Series PLC is not connected, the
connection mode for the A Series PLC is selected.
• Cause
Check for the A or Q Series was executed, the
connection mode was automatically changed over,
then the device range was checked.
This error occurs when the device range set on the
head screen is beyond the range for the Q Series.
(The head screen is the screen No. 1 in the GT
Designer, and the screen No. 0 in the DU/WIN.)
• Countermeasures
Connect the PLC.
There is not data because the unit is new or the
memory clear has been executed.
• Cause
There is no screen data.
• Countermeasures
Write the screen data using the screen creation
software.
From
first
product
6.00 or
later
4.00 or
later
From
first
product
"CAN NOT WRITE
TO PLC MEMORY."
is displayed on the
GOT-F900 screen.
This error is not displayed.
Earlier
than
1.10
Earlier
than
6.10
Earlier
than
4.10
−
"CAN NOT WRITE."
is displayed on the
GOT-F900 screen.
This error is not displayed.
1.10 or
later
6.10 or
later
4.10 or
later
From
first
product
"CAN NOT USE THE
FUNCTION WHILE
PROTECTED." is
displayed on the
GOT-F900 screen.
This error is not displayed.
From
first
product
From
first
product
From
first
product
From
first
product
"PLC IS RUNNING."
is displayed on the
GOT-F900 screen.
This error is not displayed.
From
first
product
From
first
product
From
first
product
From
first
product
Contents of trouble
Check points and countermeasures
OS version
F940W
F940
F930
F920
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......