GOT-F900 SERIES (CONNECTION)
Connection of MELSEC-Q Series PLC 11
11-16
11.6
Setting of Connected Equipment for GOT
The setting for connection to the Q Series PLC can be executed using the GOT-F900 and the screen
creation software (GT Designer2, GT Designer or DU/WIN).
Setting the Connection Type
Set the connection type in accordance with the connected equipment as shown in the table below.
Have in mind that computer link for Q (serial communication unit) and Q multiple PLC system requires
CPU direct connection.
1) GOT-F900 Series
When the main menu screen change operation is disabled.
When the main menu screen change operation is enabled.
Connected equipment
[classification in manual]
GOT-F900
Screen creation
software
Remarks
CONNECTION
Type
[QCPU direct connection]
RS-232C port of QCPU card
CPU direct connection (RS-232C)
Programming port
[Q computer link]
QJ71C24 (RS-422/RS-232C)
QJ71C24-R2 (RS-232C)
CPU direct connection (RS-422) or
CPU direct connection (RS-232C)
Communicates as programming port
Operation
Display (screen name)
a)While pressing and holding the upper left corner of the screen,
turn on the power. Keep holding the upper left corner for about
25 seconds more.
Then, press "END" at the upper right corner.
The "LANGUAGE" screen appears.
The "SET-UP MODE" screen appears.
b)Press "PLC TYPE".
c) Set the following.
PLC TYPE:When monitoring only the connected CPU
QnA, Q SERIES
When monitoring other CPU via Q multiple PLC system
Q (MULTI) SERIES
CONNECTION:CPU PORT (RS-422)
CPU PORT (RS-232C)
DST STATION # (STATION #) : 00
GOT STATION # (
−
)
:
−
The "PLC TYPE" screen appears.
Operation
Display (screen name)
a)Press the upper left corner of the screen. (The position to be
pressed can be changed in the GOT and the screen creation
software.)
The "SELECT MODE" screen appears.
b)Press "OTHER MODE" on the menu.
The "OTHER MODE" screen appears.
c) Press "SET-UP MODE" on the menu.
The "SET-UP MODE" screen appears.
d)Press "PLC TYPE".
e)Set the following.
PLC TYPE:When monitoring only the connected CPU
QnA, Q SERIES
When monitoring other CPU via Q multiple PLC system
Q (MULTI) SERIES
CONNECTION:CPU PORT (RS-422)
CPU PORT (RS-232C)
DST STATION # (STATION #) : 00
GOT STATION # (
−
)
:
−
The "PLC TYPE" screen appears.
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......