GOT-F900 SERIES (CONNECTION)
Connection of MELSEC-A Series PLC 9
9-8
9.3
Setting in A Computer Link Connection
In A computer link connection, the switches in the computer link unit (shown in the following page)
should be set as described below.
9.3.1
Communication Setting Specifications
1) Setting the mode selector switch
Set the mode so that the COM port of the computer link unit connected to the GOT-F900 is set to the
dedicated protocol format 1.
2) Setting the transmission specifications setting switches
Set the transmission specifications setting switches of the computer link unit to realize the
transmission specifications shown in the table below.
- The specifications such as the transmission speed are fixed on the GOT-F900 side, and cannot be
changed.
3) Setting the station number setting switches
Match the switches to the value set in the GOT-F900 (0 to 15).
(In some computer link units, the switches should be set in the range from 0H to FH.)
4) Turning on the power again
After setting the A computer link, make sure to turn off the power once, then turn it on again.
(Even if the RESET switch in the ACPU is pressed, the changed setting does not become valid.)
COM port
Set value
Remarks
RS-422
5
RS-422: Format 1
RS-232C: No protocol
RS-232C
1
RS-422: No protocol
RS-232C: Format 1
Item
Set value
Remarks
Transmission speed
19,200 bps
Data
format
Data bit
7 bits
Parity bit
Provided (even)
Stop bit
1 bit
Sum check
Provided
Write in RUN mode
Possible
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......