GOT-F900 SERIES (CONNECTION)
Connection of Peripheral Equipment 6
6-14
2) Program
Classification
Contents of trouble
Check points and countermeasures
GX Developer,
FXGP/WIN or
dedicated
machine
Sequence program transfer/
monitoring is disabled.
The RS-232C port of the GOT-F900 is allocated to
another connected equipment (bar code reader printer).
• Causes
1)"RS-232C" is specified for PLC connection.
2)The bar code reader is set valid.
3)The printer is set valid.
Confirm the settings above in the screen creation
software.
• Countermeasures
Against 1), set PLC connection to RS-422. Or select a
model equipped with two built-in RS-232C ports (such
as the F943GOT-SBD-H).
Against 2) and 3), Change the setting in the screen
creation software.
The sequence programming tool (dedicated machine) is
connected to the RS-422 port of the GOT-F900.
• Cause
The sequence programming tool (dedicated machine)
cannot be connected to the RS-422 port of the GOT-F900.
• Countermeasures
Only a personal computer can be connected to the RS-
232C port. (The dedicated machine can be connected
using the two-port interface FX-2PIF.)
GX Developer
only
When transfer is executed by the GX
Developer, a communication error
sometimes occurs.
The GOT-F900 does not support the GX Developer (only
in the initial version of the F940GOT).
• Cause
The version of the GOT-F900 is earlier than 1.00 and
does not correspond to the GX Developer.
• Countermeasures
Check the OS version of the GOT-F900, and upgrade
the OS.
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......