GOT-F900 SERIES (CONNECTION)
Connection of MELSEC-F FX Series PLC 8
8-6
8.3
Cautions on Use of MELSEC-F FX Series
When using the GOT-F900 connected to the FX Series PLC, observe the following cautions on use.
8.3.1
Device specification
The device range specifications vary depending on the model of the FXCPU.
Input relays (X) X000 to X377 can be read only.
It is not allowed to specify a bit device as a word device or specify a word device as a bit device.
For the details, refer to section 3.3.
8.3.2
Devices which can be monitored
Specify the device No. of input relays (X) and output relays (Y) in octal (1, 2, 3 ... 7, 10, 11 ... 17, 20).
Specify the device No. of other devices in decimal.
Only devices described in "3.3 Device Names Which can be Monitored" can be specified.
8.3.3
When GOT-F900 is connected to optional port
By connecting the appropriate module to the FX Series PLC (see table below), the GOT-F900 can be
connected to the optional port.
In this case, set the GOT-F900 to CPU direct connection. No setting is required in the FX Series PLC
because programming communication is specified at the time of shipment from the factory.
These optional por ts enable communication using either communication protocol, no protocol
communication, computer link, easy PLC link, parallel link and programming.
For connecting the GOT-F900, the programming communication mode should be selected (which is set
at the time of shipment from the factory). If any other protocol or an improper protocol has been set,
release the setting (by a sequence program or the software) while referring to the procedure below.
1) To set by a sequence program
-
Delete the no protocol communication (RS instruction).
-
Delete programs set by computer link, easy PLC link and parallel link.
-
Delete the setting of communication parameters (D8120). (If the parameters are set using the
software for sequence program, refer to the description on the setting by the software also.)
For the details on the program settings, refer to the "FX COMMUNICATION (RS-232C/RS-422)
USER'S MANUAL".
FX Series PLC
FX
1S
FX
0N
FX
1N
FX
2N
FX
2NC
Option
FX
0N
-232ADP
$
−
$
$
$
FX
0N
-485ADP
−
−
−
−
−
FX
1N
-232-BD
$
−
$
−
−
FX
1N
-422-BD
$
−
$
−
−
FX
1N
-485ADP
−
−
−
−
−
FX
2N
-232-BD
−
−
−
$
−
FX
2N
-422-BD
−
−
−
$
−
FX
2N
-485ADP
−
−
−
−
−
FX
2NC
-232ADP
$
−
$
$
$
FX
2NC
-485ADP
−
−
−
−
−
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......