5) In the case of CPM2C Series (CPU equipped with built-in peripheral port)
In the CPU CPM2C-10CDR-D, write data to the data memory (DM) shown in the table below using a
peripheral tool. In the CPU CPM2C-10CDR-D, set the DIP switch shown below.
The table below explains the data memory (DM) Nos. and set values which should be set using a
peripheral tool.
Setting item
Set value
Remarks
CPM2C-10CDR-D
DIP switch SW1
OFF
Setting item
Port
Set value (hexadecimal)
Remarks
Communication
DM6645
0001H
Communication condition: Set individually
Host link mode
CTS control: Not provided
Transmission speed
DM6646
0304H
Baud rate: 19200 bps
Start bit length: 1 bit
Data length: 7 bits
Stop bit length: 2 bits
Parity: Even
Transmission delay time
DM6647
0000H
Transmission delay time: 0ms
Unit number
DM6648
0000 to 0031
Host link unit number (BCD value)
No protocol
communication
DM6649
0000H
Default (effective according to no protocol.)
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......