Error Code Description
Action/
Possible Failing FRU
1017 CDC6 A power short has been detected in the DASD
subsystem in an I/O drawer.
Go to “MAP 1520: Power” on page 144.
1017 F4x6 Hardware configuration does not support
N-mode power.
Call Service Support
1017 F516 An N+1 boundary (DCA or fan) has dropped to
N-mode status in the fourth I/O subsystem,
location: U1.13.
This is normally an informational message. It
should be accompanied by other error codes
that more precisely indicate where the failure is.
Examine the service processor error log. If there
are no other power-related error codes (in the
time frame in which this code was generated) in
the service processor error log, the FRU
indicated with this error code, if any, should be
replaced.
1017 F526 An N+1 boundary (DCA or fan) has dropped to
N-mode status in the fourth I/O subsystem,
location: U1.13.
This is normally an informational message. It
should be accompanied by other error codes
that more precisely indicate where the failure is.
Examine the service processor error log. If there
are no other power-related error codes (in the
time frame in which this code was generated) in
the service processor error log, the FRU
indicated with this error code, if any, should be
replaced.
1017 xx11 Fourth I/O subsystem in primary rack (no IBF),
DCA-1
U1.13-V1
1017 xx13 Seeprom fault on DCA-1 in fourth I/O subsystem
(no IBF) in primary rack
U1.13-V1
1017 xx15 Fourth I/O subsystem in primary rack (no IBF)
If there is no DCA in U1.18-P1-V8, primary rack,
no IBFs go to “MAP 1520: Power” on page 144
with these pairs of location codes:
1. U1.13-V1/Q1 and U1.35-P2-X3/Q7
2. U1.13-V1/Q2 and U1.35-P1-X3/Q7
If there is a 6th DCA in U1.18-P1-V8, go to
“MAP 1520: Power” on page 144 with these
pairs of location codes:
1. U1.13-V1/Q1 and U1.35-P2-X2/Q9
2. U1.13-V1/Q2 and U1.35-P1-X2/Q9
1017 xx17 Problem with fan 1 and fan 3 in fourth I/O
subsystem (no IBF installed) in primary rack
1. DCA-1
Location U1.13-V1
2. Fan 1,
Location U1.13-F1
3. Fan 3,
Location U1.13-F3
1017 xx21 Fourth I/O subsystem in primary rack (no IBF),
DCA-2
U1.13-V2
1017 xx23 Seeprom fault on DCA-2 in fourth I/O subsystem
(no IBF) in primary rack
U1.13-V2
Chapter 5. Error Code to FRU Index
369
Summary of Contents for pSeries 670
Page 1: ...pSeries 670 Service Guide SA38 0615 03 ERserver...
Page 2: ......
Page 3: ...pSeries 670 Service Guide SA38 0615 03 ERserver...
Page 12: ...x Eserver pSeries 670 Service Guide...
Page 16: ...xiv Eserver pSeries 670 Service Guide...
Page 18: ...xvi Eserver pSeries 670 Service Guide...
Page 324: ...Yes Go to Step 154A 14 on page 302 304 Eserver pSeries 670 Service Guide...
Page 718: ...698 Eserver pSeries 670 Service Guide...
Page 848: ...L3 Cache Shorts Test Step 4 828 Eserver pSeries 670 Service Guide...
Page 849: ...L3 Cache Shorts Test Step 5 Chapter 9 Removal and Replacement Procedures 829...
Page 851: ...L3 Cache Shorts Test Step 2 Chapter 9 Removal and Replacement Procedures 831...
Page 853: ...L3 Cache Shorts Test Step 4 Chapter 9 Removal and Replacement Procedures 833...
Page 854: ...L3 Cache Shorts Test Step 5 834 Eserver pSeries 670 Service Guide...
Page 971: ...7040 Model 671 Media Subsystem 1 2 3 4 5 6 7 8 9 10 Chapter 10 Parts Information 951...
Page 973: ...Power and SCSI Cables to the Media Subsystem 1 2 3 5 4 6 Chapter 10 Parts Information 953...
Page 986: ...966 Eserver pSeries 670 Service Guide...
Page 990: ...970 Eserver pSeries 670 Service Guide...
Page 1018: ...998 Eserver pSeries 670 Service Guide...
Page 1020: ...1000 Eserver pSeries 670 Service Guide...
Page 1028: ...1008 Eserver pSeries 670 Service Guide...
Page 1031: ......