Parameter
Setting
Notes
Parameter 13-40 Logic Rule Boolean 1
[0]
[37] Digital input DI32
–
Parameter 13-42 Logic Rule Boolean 2
[0]
[2] Running
–
Parameter 13-41 Logic Rule Operator 1
[0]
[3] AND NOT
–
Parameter 13-40 Logic Rule Boolean 1
[1]
[37] Digital input DI32
–
Parameter 13-42 Logic Rule Boolean 2
[1]
[2] Running
–
Parameter 13-41 Logic Rule Operator 1
[1]
[1] AND
–
Parameter 13-15 RS-FF Operand S
[0]
[26] Logic rule 0
Output from
parameter 13-41 Log ic Rule Operator 1
[0].
Parameter 13-16 RS-FF Operand R
[0]
[27] Logic rule 1
Output from
parameter 13-41 Log ic Rule Operator 1
[1].
Parameter 13-51 SL Controller 1 Event
[0]
[94] RS Flipflop 0
Output from
parameter 13-15 RSFF Operand S
and
parameter
13-16 RSFF Operand R
.
Parameter 13-52 SL Controller 1 Action
[0]
[22] Run
–
Parameter 13-51 SL Controller 1 Event
[1]
[27] Logic rule 1
–
Parameter 13-52 SL Controller 1 Action
[1]
[24] Stop
–
Parameter 13-15 RS-FF Operand S
Table 459: Parameter 13-15 RS-FF Operand S
13-15 RS-FF Operand S
Default Value: Size related
Parameter Type: Option, Array [10]
Setup: 2 set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Option
Name
Description
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
AU373327181955en-000101 / 130R1208 | 241
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide