4.16.2 16-1* Motor Status
Parameter 16-10 Power [kW]
Table 583: Parameter 16-10 Power [kW]
16-10 Power [kW]
Default Value: 0 kW
Parameter Type: Range, 0 - 10000 kW
Setup: All set-ups
Conversion Index: 1
Data Type: Int32
Change during operation: False
Shows motor power in kW. The value shown is calculated based on the actual motor voltage and motor current. The value is fil-
tered, and therefore approximately 1.3 s may pass from when an input value changes to when the data readout values change. The
resolution of readout value on fieldbus is in 10-W steps.
Parameter 16-11 Power [hp]
Table 584: Parameter 16-11 Power [hp]
16-11 Power [hp]
Default Value: 0 hp
Parameter Type: Range, 0 - 10000 hp
Setup: All set-ups
Conversion Index: -2
Data Type: Int32
Change during operation: False
Shows motor power in hp. The value shown is calculated based on the actual motor voltage and motor current. The value is filtered,
and therefore approximately 1.3 ms may pass from when an input value changes to when the data readout values change.
Parameter 16-12 Motor Voltage
Table 585: Parameter 16-12 Motor Voltage
16-12 Motor Voltage
Default Value: 0 V
Parameter Type: Range, 0 - 6000 V
Setup: All set-ups
Conversion Index: -1
Data Type: Uint16
Change during operation: False
View the motor voltage, a calculated value used for controlling the motor.
Parameter 16-13 Frequency
Table 586: Parameter 16-13 Frequency
16-13 Frequency
Default Value: 0 Hz
Parameter Type: Range, 0 - 6500 Hz
Setup: All set-ups
Conversion Index: -1
Data Type: Uint16
Change during operation: False
View the motor frequency without resonance damping.
Parameter 16-14 Motor Current
Table 587: Parameter 16-14 Motor Current
16-14 Motor Current
Default Value: 0 A
Parameter Type: Range, 0 - 10000 A
Setup: All set-ups
Conversion Index: -2
Data Type: Int32
Change during operation: False
View the motor current measured as an average value, I
RMS
. The value is filtered, and thus approximately 1.3 s may pass from when
an input value changes to when the data readout values change.