Parameter 4-56 Warning Feedback Low
Table 257: Parameter 4-56 Warning Feedback Low
4-56 Warning Feedback Low
Default value: Size related Parameter type: Range, par 4-57 - -999999.999 ReferenceFeedback-
Unit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the lower feedback limit. When the feedback drops below this limit, the display reads Feedb
Low
. The signal outputs can be
programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02.
Parameter 4-57 Warning Feedback High
Table 258: Parameter 4-57 Warning Feedback High
4-57 Warning Feedback High
Default value: Size related Parameter type: Range, par 4-56 - 999999.999 ReferenceFeedback-
Unit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb
High
. The signal outputs can be pro-
grammed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02.
Parameter 4-58 Missing Motor Phase Function
Table 259: Parameter 4-58 Missing Motor Phase Function
4-58 Missing Motor Phase Function
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
N O T I C E
This parameter cannot be adjusted while the motor is running.
The function detects missing motor phase while the motor is running. Shows alarms 30, 31, 32 if a motor phase is missing. Enable
this function to protect the application and motor from malfunctioning if a motor phase is missing.
Op-
tion
Name
Description
[0]
Disabled
The drive does not issue a missing motor phase alarm.
[1]
Trip 100 ms
The drive performs a scan for 100 ms to detect missing motor phase. When a missing motor phase is
detected, the drive trips. This selection is recommended when the motor is running at a speed of 10 Hz
and above.
[2]
Trip 1000
ms
The drive performs a scan for 1000 ms to detect missing motor phase. When a missing motor phase is
detected, the drive trips. This selection is recommended when the motor is running at a low speed rang-
ing from 1–10 Hz.
[3]
Trip 100 ms
3ph detec.
N O T I C E
Only available in flux closed loop.
AU373327181955en-000101 / 130R1208 | 135