Parameter 5-40 Function Relay
Table 313: Parameter 5-40 Function Relay
5-40 Function Relay
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select options to define the function of the relays. Relay 1 [0], relay 2 [1].
Option Name
Description
[0]
No operation
All digital and relay outputs are by default set to No Operation.
[1]
Control ready
The control card is ready.
[2]
Drive ready
The drive is ready to operate. Mains and control supplies are OK.
[3]
Drive rdy/rem ctrl
The drive is ready for operation and is in auto-on mode.
[4]
Enable/no warning
Ready for operation. No start or stop commands have been applied (start/disable). No warn-
ings are active.
[5]
Running
The motor is running, and shaft torque is present.
[6]
Running/no warning
Output speed is higher than the speed set in
parameter 1-81 Min Speed for Function at Stop
[RPM]
. The motor runs and there are no warnings.
[7]
Run in range/no warn The motor runs within the programmed current and the speed ranges set in
parameter 4-50
Warning Current Low
and
parameter 4-53 Warning Speed High
. No warnings.
[8]
Run on ref/no warn
The motor runs at reference speed. No warnings.
[9]
Alarm
An alarm activates the output. No warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit
Generator Mode
has been exceeded.
[12]
Out of current range
The motor current is outside the range set in
parameter 4-18 Current Limit
.
[13]
Below current, low
The motor current is lower than set in
parameter 4-50 Warning Current Low
.
[14]
Above current, high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[15]
Out of speed range
Output speed/frequency is outside the frequency range set in
parameter 4-52 Warning Speed
Low
and
parameter 4-53 Warning Speed High
.
[16]
Below speed, low
Output speed is lower than the setting in
parameter 4-52 Warning Speed Low
.
[17]
Above speed, high
Output speed is higher than the setting in
parameter 4-53 Warning Speed High
.
[18]
Out of feedb. range
Feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and
parameter 4-57
Warning Feedback High
.
[19]
Below feedback, low
Feedback is below the limit set in
parameter 4-56 Warning Feedback Low
.
[20]
Above feedback, high Feedback is above the limit set in
parameter 4-57 Warning Feedback High
.
[21]
Thermal warning
Thermal warning turns on when the temperature exceeds the limit either in motor, drive,
brake resistor, or connected thermistor.
[22]
Ready,no thermal W
The drive is ready for operation and there is no overtemperature warning.
AU373327181955en-000101 / 130R1208 | 165
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide