Option Name
Description
[1644]
Speed Error [RPM]
[1645]
Motor Phase U Current
[1646]
Motor Phase V Current
[1647]
Motor Phase W Current
[1648]
Speed. Ref. After Ramp [RPM]
[1650]
External Reference
Sum of the external reference as a percentage, that is, the sum of analog/pulse/bus.
[1651]
Pulse Reference
Frequency in Hz connected to the digital inputs (18, 19 or 32, 33).
[1652]
Feedback[Unit]
Reference value from programmed digital inputs.
[1653]
Digi Pot Reference
[1657]
Feedback [RPM]
[1660]
Digital Input
Signal states from the 6 digital terminals (18, 19, 27, 29, 32, and 33). There are 16 bits
in total, but only 6 of them are used. Input 18 corresponds to the far left of the used
bits. Signal log=0; Signal high=1.
[1661]
Terminal 53 Switch Setting
Setting of input terminal 54. Current=0; Voltage=1.
[1662]
Analog Input 53
Actual value at input 53 either as a reference or protection value.
[1663]
Terminal 54 Switch Setting
Setting of input terminal 54. Current=0; Voltage=1.
[1664]
Analog Input 54
Actual value at input 54 either as reference or protection value.
[1665]
Analog Output 42 [mA]
Actual value at output 42 in mA. Use
parameter 6-50 Terminal 42 Output
to select the
value to be shown.
[1666]
Digital Output [bin]
Binary value of all digital outputs.
[1667]
Freq. Input #29 [Hz]
Actual value of the frequency applied at terminal 29 as an impulse input.
[1668]
Freq. Input #33 [Hz]
Actual value of the frequency applied at terminal 33 as an impulse input.
[1669]
Pulse Output #27 [Hz]
Actual value of impulses applied to terminal 27 in digital output mode.
[1670]
Pulse Output #29 [Hz]
Actual value of impulses applied to terminal 29 in digital output mode.
[1671]
Relay Output [bin]
[1672]
Counter A
Application-dependent (for example, SLC control).
[1673]
Counter B
Application-dependent( for example, SLC control).
[1674]
Prec. Stop Counter
Shows the actual value of the counter.
[1675]
Analog In X30/11
Actual value at input X30/11 either as reference or protection value.
[1676]
Analog In X30/12
Actual value at input X30/12 either as reference or protection value.
[1677]
Analog Out X30/8 [mA]
Actual value at output X30/8 in mA. Use
parameter 6-60 Terminal X30/8 Output
to se-
lect the value to be shown.
[1678]
Analog Out X45/1 [mA]
[1679]
Analog Out X45/3 [mA]
AU373327181955en-000101 / 130R1208
40 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide