Option
Name
Description
[4]
Digital input 19
[5]
Digital input 32
[6]
Digital input 33
Parameter 1-95 Thermistor Sensor Type
Table 139: Parameter 1-95 Thermistor Sensor Type
1-95 Thermistor Sensor Type
Default value: [0] KTY Sensor 1
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the used type of thermistor sensor.
Option
Name
Description
[0]*
KTY sensor 1
1 kΩ at 100 °C (212 °F).
[1]
KTY sensor 2
1 kΩ at 25 °C (77 °F).
[2]
KTY sensor 3
2 kΩ at 25 °C (77 °F).
[3]
Pt1000
[4]
Ni1000 (6178 ppm/K)
[5]
Ni1000-LG (TC5)
Examples:
Siemens LG-Ni1000
Tasseron RTD Ni1000-TC5 1000 Ohm
Parameter 1-96 Thermistor Sensor Resource
Table 140: Parameter 1-96 Thermistor Sensor Resource
1-96 Thermistor Sensor Resource
Default value: [0] None
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Selecting analog input terminal 54 to be used as thermistor sensor input. Terminal 54 cannot be selected as thermistor source if
otherwise used as reference (see
parameter 3-15 Reference Resource 1
to
parameter 3-17 Reference Resource 3
).
N O T I C E
Connection of thermistor sensor between terminals 54 and 55 (GND).
Option
Name
Description
[0]*
None
[2]
Analog input 54
AU373327181955en-000101 / 130R1208 | 91
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide