Option
Function
[84]
SL digital output E
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[42] Set dig. out. E high
is executed. The output goes low whenever the smart logic action
[36] Set
dig. out. E low
is executed.
[85]
SL digital output F
See
parameter 13-52 SL Controller Action
. The output goes high whenever the smart logic action
[43] Set dig. out. F high
is executed. The output goes low whenever the smart logic action
[37] Set
dig. out. F low
is executed.
[90]
kWh counter pulse
Sends a pulse (200 ms pulse width) to output terminal whenever kWh counter changes (
parame-
ter 15-02 kWh Counter
).
[120] Local ref active
Output is high when
parameter 313 Reference Site
=
[2] Local
.
Table 309: Local Reference Active
Reference site set in
parameter 3-13 Reference Site
Local reference active [120]
Remote reference active [121]
Reference site: Local
parameter 3-13 Reference Site [2] Local
1
0
Reference site: Remote
parameter 3-13 Reference Site [1] Remote
0
1
Reference site: Linked to Hand/ Auto
–
–
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 310: 5-30 Digital Outputs - 2
Option
Function
[121] Remote ref active
Output is high when
parameter 3-13 Reference Site
=
[1] Remote
or
[0] Linked to hand/auto
while
the LCP is in auto-on mode. See
.
[122] No alarm
Output is high when no alarm is present.
[123] Start command active
Output is high when there is an active start command (that is via digital input bus connection,
hand-on, or auto-on), and no stop or start command is active.
[124] Running reverse
Output is high when the drive runs counterclockwise (the logical product of the status bits run-
ning AND reverse).
[125] Drive in hand mode
Output is high when the drive is in hand-on mode (as indicated by the LED light above [Hand
On]).
[126] Drive in auto mode
Output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto
On]).
[180] Clock fault
[181] Prev. maintenance
[188] AHF capacitor connect The capacitors are turned on at 20% (hysteresis of 50% gives an interval of 10– 30%). The capaci-
tors are disconnected below 10%. The off delay is 10 s and restarts if the nominal power goes
above 10% during the delay.
Parameter 5-80 AHF Cap Reconnect Delay
is used to guarantee a
minimum off time for the capacitors.