4.1.4 0-3* LCP Custom Readout
It is possible to customize the display elements for various purposes:
Custom readout. Value proportional to speed (linear, squared, or cubed depending on the unit selected in
parameter 0-30 Cus-
tom Readout Unit
.
Display text. Text string stored in a parameter.
Custom reaout
The calculated value to be shown is based on the settings in:
Parameter 0-30 Custom Readout Unit
.
Parameter 0-31 Custom Readout Min Value
(linear only).
Parameter 0-32 Custom Readout Max Value
.
Parameter 4-13 Motor Speed High Limit [RPM]
.
Parameter 4-14 Motor Speed High Limit [Hz]
.
Actual speed.
e
3
0
b
t1
0
5
.1
2
0
Lin
ea
r U
nit
(e
.g.
sp
ee
d a
nd
flo
w)
Q
ua
dr
at
ic
Un
it
(P
re
ssu
re
)
C
ub
ic
U
ni
t (
P
ow
er
)
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
P 0-31
Linear
units only
Motor Speed
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
Illustration 26: Custom Readout
The relation depends on the type of unit selected in
parameter 0-30 Custom Readout Unit
.
Table 22: Speed Relations for Different Unit Types
Unit type
Speed relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Quadratic
Power
Cubic